banner
Orange County - Los Angeles County - Riverside County - San Bernardino County

Home | Fire Doors | Rolling Steel Fire Doors | Fire Doors, Frames & Hardeware | Counter Shutter Fire Door
NFPA 80 | Fire Door Inspections | Drop Testing | Request a Quote

Fire Rated Wood Door

Fire Rated Metal Door

Fire Dept

Fire Door Inspection
Swinging Doors

All Fire Doors Are Required By NFPA 80 To Be Inspected Annually

NFPA 80 5.2.4.2 as a minimum, the following items shall be verified:

  1. No Open Holes or breaks exist in surfaces of either the door or frame
  2. Glazing, vision light frames, & glazing beads are intact and securely fastened in place, if so equipped.
  3. The door, frame, hinges, hardware, and noncombustible threshold are secured, aligned, and in working order with no visible sings of damage.
  4. No parts are missing or broken.
  5. Door clearances at the door edge of the door frame, on the pull side of the door, do not exceed clearances listed in 4.8.4 (the clearance under the bottom of the door shall be a maximum of 3/4in) and 6.3.1 (top & edges 1/8in)
  6. The self-closing device is operational, that is, the active door completely closes when operated from the full open position.
  7. If a coordinator is installed, the inactive leaf closes before active leaf.
  8. Latching hardware operates and secures the door when it is in the closed position.
  9. Auxiliary hardware items that interfere or prohibit operation are not installed on the door or frame.
  10. No field modifications to the door assembly have been performed that void the label.
  11. Gasketing and edge seals, where required, are inspected to verify their presence and integrity.

Call us today a Free Estimate (800) 698-7202

Orange County
370 E. Orangethorpe Ave.
Placentia, Ca. 92870
(714) 961-1141
(714) 961-1140 fax
Inland Empire
1620 S. Carlos Ave
Ontario, Ca 91761
(909) 861-2144
(909) 923-7279 Fax

fire test label

NFPA 80 4.2.2: Labels shall be applied in locations that are readily visible and convenient for identification by the AHJ (authority having jurisdiction) after installation of the assembly